Remote

Termination

Panel (RTP)

channel 2

19621

Each channel has four connections: R, I, O, and S.
Field wiring to the RTP is the same for all RTP variations.
Channel 1 uses R1, I1, O1, and S1; channel 2 uses R2, I2,
O2, and S2; and so on for the remaining channels.

I = input

O = output

Field Wiring

S = shield

channel 1

R = return

4

1. Strip 3/8 inch (9.25 mm) of insulation from

the 22-12 AWG wire.

2. Insert the wire into the open connector slot.

3. Tighten the screw to clamp the wire.

Connect Wiring to the Remote
Termination Panel

The 1897-NOV module is cable-connected to a 1771-RTP4
remote termination panel using cat. no. 1771-NC6 (6 ft) or
-NC15 (15 ft) cables. This RTP has straight-through wiring. The
remote termination panel mounts on standard DIN 1 or DIN 3
mounting rails.

Fast Isolated Analog Output Module

5

Publication CIG-5.1 – April 1998

Output

Type

Connect

To

+

O1

Output

Voltage

-

R1

Return

Shield

S1

Shield

RTP End of

1771-NC cable

11024-I

RTP4

DIN R

Channel 1 Connections
R1 = Return 1
I1 = Input 1
O1 = Output 1
S1 = Shield 1

Note: Terminals W1, W2
and W3 are spares.
Do not use terminals CR
and CL.

Example:

Connect the Cables to the
Remote Termination Panel

5

1. Insert the RTP end of the cable into the connector

on the the RTP.

2. Alternately tighten the retaining screws into

the connector on the RTP until secure.

Screw