Remote termination panel dimensions, Building your own cables – Rockwell Automation 1897-NOV High Speed Analog Installation Instructions User Manual
Page 6

Fast Isolated Analog Output Module
6
Publication CIG-5.1 – April 1998
5.30
(134.6)
3.0
(75.0)
2.3
(58.4)
RTP4
1
2.3
(58.4)
Dimensions
back of
DIN rail
Inches
(Millimeters)
J1
J2
J3
J4
J8
J7
J6
J5
A
B
Remote Termination Panel Dimensions
Building Your Own Cables
You can terminate the analog module to a terminal block by cutting
the 25-pin RTP end connector off the standard cable and wiring to
your terminal block. Refer to the following table for wire termination
designations.
Wire Termination Designations
Module Top Connector
Module Bottom Connector
Channel Number
Signal
37-Pin Connector
Wire Color
Channel Number
Signal
37-Pin Connector
Wire Color
I1
20
Blk
I5
20
Blk
1
O1
22
Blk/Wht
5
O5
22
Blk/Wht
R1
21
Wht/Blk
R5
21
Wht/Blk
I2
24
Orn
I6
24
Orn
2
O2
26
Orn/Blk
6
O6
26
Orn/Blk
R2
25
Wht
R6
25
Wht
I3
29
Grn
I7
29
Grn
3
O3
31
Grn/Blk
7
O7
31
Grn/Blk
R3
30
Grn/Wht
R7
30
Grn/Wht
I4
33
Blu
I8
33
Blu
4
O4
35
Blu/Blk
8
O8
35
Blu/Blk
R4
34
Blu/Wht
R8
34
Blu/Wht
Not used
36
Red
37