Fast Isolated Analog Output Module

6

Publication CIG-5.1 – April 1998

5.30

(134.6)

3.0

(75.0)

2.3

(58.4)

RTP4

1

2.3

(58.4)

Dimensions

back of

DIN rail

Inches

(Millimeters)

J1
J2
J3
J4

J8
J7
J6
J5

A

B

Remote Termination Panel Dimensions

Building Your Own Cables

You can terminate the analog module to a terminal block by cutting
the 25-pin RTP end connector off the standard cable and wiring to
your terminal block. Refer to the following table for wire termination
designations.

Wire Termination Designations

Module Top Connector

Module Bottom Connector

Channel Number

Signal

37-Pin Connector

Wire Color

Channel Number

Signal

37-Pin Connector

Wire Color

I1

20

Blk

I5

20

Blk

1

O1

22

Blk/Wht

5

O5

22

Blk/Wht

R1

21

Wht/Blk

R5

21

Wht/Blk

I2

24

Orn

I6

24

Orn

2

O2

26

Orn/Blk

6

O6

26

Orn/Blk

R2

25

Wht

R6

25

Wht

I3

29

Grn

I7

29

Grn

3

O3

31

Grn/Blk

7

O7

31

Grn/Blk

R3

30

Grn/Wht

R7

30

Grn/Wht

I4

33

Blu

I8

33

Blu

4

O4

35

Blu/Blk

8

O8

35

Blu/Blk

R4

34

Blu/Wht

R8

34

Blu/Wht

Not used

36

Red

37

Red/Wht