Rockwell Automation T7485 ICS Regent+Plus Isolated Guarded Output Modules User Manual
Page 11
 
Isolated Guarded Digital Output Module (T7485)
 
P D - 7 0 3 4 M a r - 0 6  
11
In general, each output circuit is rated for 1.5 Amps from 0 to 
40º C, derated linearly to 1.0 Amps at 60º C. All eight outputs 
can simultaneously operate at these levels, producing a total 
module current rating (total of all eight output circuits) of 12 
Amps from 0 to 40º C, derated linearly to 8 Amps at 60º C. 
Applications that require higher output current ratings are 
allowable, but only if the total module current is reduced. You 
may operate output circuits as high as 2.0 Amps from 0 to 40º 
C, derated to 1.5 Amps at 60º C if you reduce the current on 
the other remaining outputs. For example the combination of 
output load ratings shown in Table 2 are allowable. 
Table 2. Output Current Ratings.
0 to 40º C
at 60º C
Circuit
0 < Iout < 1.5 1.5 < Iout < 2 0 < Iout < 1.5 1.5 < Iout < 2
1
1.5
0.75
1.0
1.5
2
1.5
2.0
1.0
0.5
3
1.5
0.5
1.0
1.5
4
1.5
2.0
1.0
0.5
5
1.5
0.5
1.0
0.5
6
1.5
1.0
1.0
0.5
7
1.5
0.75
1.0
0.5
8
1.5
0.5
1.0
0.5
Total
(Imod)
12
8
(maximum @
0 - 40º C)
8
6
(maximum @
60º C)
Output Load Types
The isolated Guarded output module is ideally suited for 
controlling safety critical loads including motor starters as 
large as NEMA Size 5. Their are some applications that may 
not be suitable for using the isolated Guarded output module 
which are described below. For these applications, other 
output module types available for the system should be 
considered. Refer to the specific Product Descriptions of these 
modules for their application and specifications.