Isolated Guarded Digital Output Module (T7485)
 
P D - 7 0 3 4 M a r - 0 6  
17
Output Module Definition
In addition to configuring output point definitions, you can 
configure the output module definition to represent the 
combined state of all eight output points. 
The module definition represents the eight output point 
definitions as signed, 16-bit integers. In this format, the eight 
outputs are the least significant bits with output point 1 as the 
LSB. The eight most significant bits are always zero. 
The module definition names are not normally used for 
control purposes. However, they do provide convenient single 
name references to all eight outputs points when reporting 
status information to operator interface equipment. 
Programming
Outputs are controlled by writing application programs that 
solve for output values. For example, placing an output tag 
name on a coil in ladder logic will cause the output to turn on 
when there is power flow to the coil in the ladder logic rung. 
To program fault tolerant outputs two output coils driven by 
the same control logic are used as shown in Figure 10. 
Figure 10. Programming Fault Tolerant Outputs.
In this illustration A, B, C, D represent various logic elements 
used to drive the outputs; XV103A represents the output on 
one Guarded output module; and XV103B represents the 
output on the other Guarded output module. 
Maintenance
No periodic maintenance or calibration is required for this 
module. 
Fuses can be removed and replaced without removing the 
module from the I/O chassis. Turning the fuse holder one-