Field wiring – Rockwell Automation T7485 ICS Regent+Plus Isolated Guarded Output Modules User Manual
Page 12
 
Isolated Guarded Digital Output Module (T7485)
 
1 2  
Industrial Control Services
Resistive Loads
If resistive loads are applied, the isolated Guarded output 
module may erroneously annunciate a module fault. This will 
occur with a single, fail-safe module configuration. In dual 
module configurations, no erroneous faults will be 
annunciated until one of the two modules has a fault or is 
removed. In either configuration, the outputs will always be 
controlled on and off correctly; however, the testing of the 
output module’s circuits will not be sensed correctly by the 
module and it will report output circuit faults. 
Other output module types should be used for safety critical 
load devices that have resistive load characteristics. 
DC Voltage, Low Current Applications
DC applications with low current loads (Iout < 100 mA) and 
long field wiring lengths (Ltotal > 2000 feet) may also cause 
erroneous fault annunciation and should be avoided. Other 
output module types should be considered for these 
applications. 
Field Wiring
For field wiring details, refer to PD-7901 - I/O Termination 
Assembly (ITA).