Rockwell Automation T7485 ICS Regent+Plus Isolated Guarded Output Modules User Manual
Page 19
 
Isolated Guarded Digital Output Module (T7485)
 
P D - 7 0 3 4 M a r - 0 6  
19
Minimum Load
20 mA
Over Voltage Protection
Continuous:
 
450 VAC 
Output Test Load Bump
Single module:
 
 
 
Dual modules:
None for turn-on test. 
2 pulses at 125 msec each for 
turn-off test or if single fault. 
None during turn-on or turn-
off test. 
2 pulses at 125msec each if 
single fault. 
Fusing
One 3 A, 250 V fast-acting 
per output (Littelfuse 3AG 
series) 
Output Leakage
1 mA, maximum
Turn-On Delay
1.0 ms
Turn-Off Delay
1.0 ms
Heat Dissipation
25 Watts, 85 BTUs/hour
Isolation
2500 volts minimum (field 
wiring to control logic) 
2500 volts minimum (output 
to output) 
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity, 
non-condensing 
Vibration
10 to 55 Hz:
 
±0.15mm 
Shock
Operating:
 
15 g, ½ sine wave, 11 msec