Soe communications port configuration, Figure 5 port configuration window, Trusted – Rockwell Automation T8013 Trusted SOE and Process Historian Package User Manual
Page 11: Soe and process historian package t8013

Trusted
TM
SOE and Process Historian Package T8013
Issue 16 April 2010
PD-T8013
11
3.1. SOE Communications Port Configuration
The ports on the Trusted
TM
TMR Communications Interface module may be configured to allow SOE
data collection using serial comms or via the Ethernet. The required method is chosen by first
selecting the ‘Configure Port’ option from the ‘File’ menu.
Selecting serial ports COM 1 and 2 enable the selection of Baud rate and parity.
Selection of Ethernet permits the selection of the target system IP address and port number. In almost
every case, the port number should be left at 2000.
Note that the Communications Interface must have a Modbus slave configured in the parameters for
the module in the system configuration. The disconnection timeout must be set to 300 seconds to
prevent the connection from being lost during data retrieval. In the Communications Interface Modbus
Slave window, select a Modbus Slave and check ‘Use This Slave’. The defaults will work with the SOE
collector. Refer to product description PD-8151B.
Figure 5 Port Configuration Window