SOE and Process Historian Package T8013

Issue 16 April 2010

PD-T8013

18

3.10.2.

Intermediate SOE Variables

To select intermediate variables for collection by the SOE, the user must first declare an soe board
from the board library within the IEC1131 TOOLSET I/O connection.

Double click on a free number in the I/O Connection. Select boards, find soe and select OK. This will
enter an soe board in the I/O Connection table as shown in Figure 10 below.

Figure 10 Entering an SOE board

Once defined, the user enables soe logging by attaching the intermediate variable to a channel on this
board.

Note: Intermediate soe variables have to be declared as outputs in the dictionary.

Double click on the appropriate channel of the soe board. This will display all the internal output
variables available for soe collection as shown in Figure 11 below.

Figure 11 SOE Board Connection

The variable may now be attached to this channel by selecting the Connect button or by double
clicking on the tagname.