Unlike a Boolean SOE variable which may be attached to any I/O board within the application program,
an analogue SOE variable must be attached to the STATE rack of a High Integrity I/O board as defined
in the application program and shown in Figure 14 below.
Figure 14 STATE I/O Connection board
Double clicking the mouse on the selected channel will provide the user with a list of unattached
variables as shown in Figure 15 below.
Figure 15 STATE board connection
The variable may now be attached to the channel by selecting the Connect button. By default, each
channel attached to the STATE rack of a High Integrity I/O board only has seven values. These states
are defined in the SOE Collector as shown in Table 2 below.
0
Under Range
1
Low Low
2
Low
3
Normal
4
High
5
High High
6
Over Range
Table 2 SOE State Definitions
The SOE collector will display the string defined above for each state as changes occur.