3.1. Module Configuration

There is no configuration required to the physical module. All configurable characteristics of the
module are performed using tools on the EWS and become part of the application or system.ini file
that is loaded into the TMR Processor. The TMR Processor automatically configures the module after
applications are downloaded and during Active/Standby changeover.

The IEC1131 TOOLSET provides the main interface to configure the Zone Interface module. Details
of the configuration tools and configuration sequence are provided in PD-8082B Trusted

TM

Toolset

Suite. There are three procedures necessary to configure the module. These are:

1. Define the necessary I/O variables for the field data and module status data using the

Dictionary Editor of the IEC1131 TOOLSET.

2. Create an I/O module definition in the I/O Connection Editor for each I/O module. The I/O

module definition defines physical information, e.g. Chassis and Slot location, and allows
variables to be connected to the I/O channels of the module.

3. Using the Trusted

TM

System Configuration Manager, define custom LED indicator modes,

per-channel default or fail-safe states, and other module settings.