3.2. T8448 Complex Equipment Definition

The 8448 I/O Complex Equipment Definition includes 10 I/O boards, referenced numerically by rack
number.

Rack I/O Board

Description

Data Type

Direction No. of

Channels

OEM Parameters

-

-

-

1

DO

Field Output Status

Boolean

Out

40

2

STATE

Field Output State

Integer

In

40

3

AI

Measured voltage

Integer

In

40

4

CI

Measured current

Integer

In

40

5

LINE_FLT

Line Fault Status

Boolean

In

40

6

DISCREP

Channel Discrepancy

Integer

In

3

7

HKEEPING

Housekeeping Registers

Integer

In

57

8

INFO

I/O Module Information

Integer

In

11

9

THRSHIN

Threshold Setting Feedback

Integer

In

9

10

THRSHOUT

Threshold Setting Command

Integer

Out

11

Table 3 Complex Equipment Definition

There are two OEM parameters included in the first rack (DO Board). These OEM parameters define
the primary module position, declaring the module’s chassis and slot location. There is no need to
define the secondary module position within the IEC1131 TOOLSET if the system will always be
started with a module in the primary position. Where systems may be required to start-up with
modules in the secondary position as the active module, e.g. primary module is not installed when
application is started, the secondary module’s position should be declared in the module definition of
the System Configuration Manager.

OEM Parameter Description

Notes

TICS_CHASSIS The number of the

Trusted

TM

Chassis

where the Primary I/O
module is installed

The Trusted

TM

Controller Chassis is 1, and

Trusted

TM

Expander Chassis are 2 to 15

TICS_SLOT

The slot number in the
chassis where the
Primary I/O module is
installed

The I/O module slots in the Trusted

TM

Controller

chassis are numbered from 1 to 8. The I/O Module
slots in the Trusted

TM

Expander Chassis are

numbered from 1 to 12.

Table 4 OEM Parameters