I/o status indicators, Table 20 i/o status leds, Trusted – Rockwell Automation T8448 Trusted TMR Zone Interface Module - 40 Channel User Manual

Page 34: Module t8448

Advertising
background image

Trusted

TM

Module T8448

Issue 14 Apr 10

PD-T8448

34

4.3. I/O Status Indicators

There are 40 channel status indicators on the module front panel, one for each field input/output.
These indicators are controlled by the FPU. The FPU receives data from each of the module slices.
The FPU performs a 2-oo-3 vote on each data bit from the slices and sets the indicators accordingly.

The input/output status indicator mode is dependent upon the numerical state of the channel. Each
state can be defined to have a particular indicator mode: off, green, red, flashing green, or flashing red.
Note that although it may be possible to specify yellow (green and red together) in the System
Configurator, this is not recommended.

The configurable indicator modes allow users to customise the status indications to suit individual
application requirements. Without customisation, the default indicator modes are as described below:

INDICATOR STATE

DESCRIPTION

Off

Output is Off or Input is Open

Green

Channel is On or Input is Closed

Green – flashing

No Output Load or Input/Output Open Circuit

Red

Output short circuit (output over current protection triggered and channel is
latched off) or input short circuit

Red – flashing

Channel fault, or no field supply voltage

Table 20 I/O Status LEDs

Note: The LEDs indicating channel status may be configured to suit user requirements by

implementing the procedure for configuring the System.INI file detailed in PD-8082B.

Advertising