Table 7 rack 2: state output bit descriptions, Table 8 rack 2: state input bit descriptions, Trusted – Rockwell Automation T8448 Trusted TMR Zone Interface Module - 40 Channel User Manual

Page 24: Module t8448

Advertising
background image

Trusted

TM

Module T8448

Issue 14 Apr 10

PD-T8448

24

The least significant 3-bits indicate the operational state of the channel. When configured as an output,
the states have the following meaning.

Value

Description

7

Channel Fault

6

Field fault (e.g. field leakage to 0V or 24V)

5

Short circuit in field wiring or load

4

Output energised (ON)

3

Open circuit in field wiring or load

2

Output de-energised (OFF)

1

No field supply voltage

0

Unused

Table 7 Rack 2: STATE Output bit descriptions

When configured as an input channel, the states are allocated to voltage ranges. The usual definition
for a digital input is as follows.

Value

Description

7

Channel Fault

6

Over Range

5

Short circuit

4

Contact Closed

3

Contact Indeterminate

2

Contact Open

1

Open Circuit

0

Under Range

Table 8 Rack 2: STATE Input bit descriptions

Note that channels configured as inputs do not have a direct Boolean indication of the input status. The
Toolset application must be programmed to recognise states 2 and 4 above as open and closed
contact input respectively. All other states are treated as fault conditions; the input status determination
in these states is application specific.