6 volts/hertz curve parameters (group 5), P-47 preset speed 7 model, P-48 preset speed 8 model – Rockwell Automation SP200 AC Drive, 1 2 Channel Analog, Preset Speed User Manual
Page 39: P-50 base voltage model

Editing Drive Parameters
7-17
7.1.6 Volts/Hertz Curve Parameters (Group 5)
Following is a volts/hertz curve diagram and the volts/hertz parameter descriptions.
P-47 Preset Speed 7
Model
A
B
C
Use this parameter to define the
commanded drive frequency when it
is selected by the control inputs and
the drive is operating in the preset
mode.
Parameter Range:
0 to 240.0 (x.x Hz)
X
Default Setting:
50.0
X
Running Access:
RW
P-48 Preset Speed 8
Model
A
B
C
Use this parameter to define the
commanded drive frequency when it
is selected by the control inputs and
the drive is operating in the preset
mode.
Parameter Range:
0 to 240.0 (x.x Hz)
X
Default Setting:
60.0
X
Running Access:
RW
Breakpoint Frequency
(P53)
Base Frequency
(P-51)
Maximum Speed
P-01)
Base Voltage
(P-50)
Breakpoint
Voltage
(P-52)
Boost Voltage
(P-54)
0
0
Volts Per Hertz Curve
P-50 Base Voltage
Model
A
B
C
Use this parameter to set the motor
rated nameplate voltage.
Parameter Range:
0 to rated drive voltage (V)
X
X
X
Default Setting:
230 or 460
X
X
X
Running Access:
RW