Rockwell Automation SP200 AC Drive, 1 2 Channel Analog, Preset Speed User Manual
Page 40

7-18
Installing and Operating the SP200 AC Drive
P-51 Base Frequency
Model
A
B
C
Use this parameter to set the motor
rated nameplate frequency.
Parameter Range:
0 to 240 (Hz)
X
X
X
Default Setting:
60
X
X
X
Running Access:
RW
P-52 Breakpoint Voltage
Model
A
B
C
Use this parameter to define the
voltage corresponding to
P-53 (Breakpoint Frequency) for a
breakpoint in the V/Hz curve.
Parameter Range:
0 to rated drive voltage (V)
X
X
X
Default Setting:
0
X
X
X
Running Access:
RW
P-53 Breakpoint Frequency
Model
A
B
C
Use this parameter to define the
frequency corresponding to
P-52 (Breakpoint Voltage) for a
breakpoint in the V/Hz curve.
Parameter Range:
0 to 240 (Hz)
X
X
X
Default Setting:
0 (breakpoint disabled)
X
X
X
Running Access:
RW
P-54 Boost Voltage
Model
A
B
C
Use this parameter to define the
amount of voltage applied to the
motor when running at 0 Hz.
Parameter Range:
0 to 20% of rated drive voltage (V)
X
X
X
Default Setting:
5% of rated drive voltage
X
X
X
Running Access:
RW