4.4

Recommended Motor Lead Lengths

The following motor lead lengths are recommended to reduce line disturbances and
noise.

Refer to instruction manual D2-3360 for detailed instructions on installing output
power wiring.

Table 4.4 – Recommended Motor Lead Lengths

Drive Power Rating

Maximum Lead Length in Feet

Carrier Frequency

2 kHz

4 kHz

8 kHz

1 HP

500

500

500

5 HP

800

500

500