Configuring the Outer Control Loop Reference
9-5
▲
Set
ANLG
OUT
3
SIG
TYPE
(P.419) to 0 to 10 volts or 4 to 20 mA, depending on
the type of input signal the dancer transducer requires.
▲
Set
ANLG
OUT
3
GAIN
ADJ
(P.420) to specify the maximum value of the analog
output when the dancer loading input is at its maximum
.
Range: 0 to 10
V
, +/-10
V
, 4 to 20 mA, 10 to 50 mA
P.419 =
Range: .500 to 1.300
P.420 =
DANCER LOADING SETUP EXAMPLE
Assumptions:
•
When
TENSION
SETPOINT
(P.854) is set to
MAXIMUM
,
TENSION
DEMAND
(P.844) is at
4095 counts.
•
When
TENSION
SETPOINT
(P.854) is set to
MINIMUM
,
TENSION
DEMAND
(P.844) is at 0
counts.
•
The pneumatic transducer uses a 4 to 20 mA input, zero loading (tension) is
equivalent to 4 mA, and maximum loading (tension) is equivalent to 20 mA.
Under these conditions:
•
Set
MAX
DANCER
LOAD
(P.831) to 4095 counts, where 4095 equals maximum web
tension.
•
Set
MIN
DANCER
LOAD
(P.832) to 0 counts, where 0 counts equals zero web
tension at 4 mA.