4-2
ControlNet Network Communication Option Board For Use With FlexPak 3000 and WebPak 3000 DC Drives
4.2
Configuring Drive Reference and Feedback Data as 
Scheduled Transfers
This section describes how to:
•
configure scheduled traffic for the drive
•
control the drive using the drive reference data
•
use scheduled drive feedback data
4.2.1 Configuring Scheduled Data Transfers
Before the drive can communicate on the ControlNet network, you must configure its 
scheduled traffic information by using some type of ControlNet configuration software. 
By configuring scheduled traffic, you define how much data the drive can send, how 
often the data is sent, and where the data is written to and read from (mapped) in the 
programmable controller.
You must configure each drive on the ControlNet network. Table 4.2 lists the 
configuration information you must enter if you are using RSNetWorx
™
and a
PLC-5
™
.
Table 4.2 – ControlNet Scheduled Traffic Configuration Fields
In this field:
Enter this information:
Node
Enter the drive’s node number that you defined in P.900.
Slot 
Message
These fields are not used by the drive.
Module
Enter FlexPak 3000 or WebPak 3000.
API
This field is read-only.
RPI
Enter how often you want to exchange scheduled data between the 
programmable controller and the drive.
Connection Type
Select “Exclusive Owner.”
FlexPak 3000 and WebPak 3000 drives do not support Multicast 
operation.
Input Address
Enter the programmable controller’s integer file number that will store 
data received from the drive (drive feedback data).
Input Size
Enter the number of words of drive feedback data that you want the 
programmable controller to receive from the drive (1 to 8). 
See section 4.2.3 for information about the type of data that is sent.
Output Address
Enter the programmable controller’s integer file number that will store 
data sent to the drive (drive reference data).
Output Size
Enter the number of words of drive reference data that you want the 
programmable controller to send to the drive (1 to 8).
See section 4.2.2 for information about the type of data that is sent.
Status Address
Enter the programmable’s integer file number that will store the status of 
the ControlNet connection to the drive.
Config Address
Config Size
These fields are not used by the drive.