Rockwell Automation Flex/WebPak 3000 DC Drive ControlNet, Network Communication Board, 915FK2101 User Manual
Page 77

Register Map for WebPak 3000 Drives
8-9
N10:218
DIG
OUT
1
CONTACT
TYP
P.410
Config
0 =
NORMAL
OPEN
1 =
NORMAL
CLOSED
N10:219
DIG
OUT
2
SELECT
P.411
Config
0 =
LEVEL
DETECTOR
OUT
1
1 =
LEVEL
DETECTOR
OUT
2
2 = At speed
3 = In current limit
4 = Drive ready
5 =
CURRENT
MEM
COMMAND
6 =
UNDERWIND
COMMAND
7 =
TENSION
COMMAND
8 =
STALL
TENSION
COMMAND
9 =
SLACK
TAKE
UP
COMMAND
10 =
DIAMETER
RESET
TP
11 =
ARMATURE
BRIDGE
POL
12 =
FIELD
ECONOMY
ACTIVE
13 =
NETW
COMM
STATUS
14 =
NETW
IN
REG
1
15 =
NETW
IN
REG
2
16 =
NETW
IN
REG
3
17 =
SPEED
PROFILER
ENABLE
18 =
DIAMETER
CALC
ENABLE
N10:220
DIG
OUT
2
CONTACT
TYP
P.412
Config
0 =
NORMAL
OPEN
1 =
NORMAL
CLOSED
N10:221
LINE
SPEED
SIG
TYPE
P.100
Config
0 = 0 to 10 V
1 = +/-10 V
2 = 4 to 20 mA
3 = 10 to 50 mA
N10:222
TENSION
SETPT
SIG
TYP
P.413
Config
0 = 0 to 10 V
1 = +/-10 V
2 = 4 to 20 mA
3 = 10 to 50 mA
N10:223
ANLG
OUT
3
SIG
TYPE
P.419
Config
0 = 0 to 10 V
1 = +/-10 V
2 = 4 to 20 mA
3 = 10 to 50 mA
Table 8.1 – File N10:x (Drive Read/Write Parameters) for WebPak 3000 Drives (Continued)
File
Address
Parameter Name
Parameter
Number
Type
Scale