_C
4-47
Power Frequency Magnetic Field immunity voltage Dips, Short interruptions and
Voltage Variations Immunity
BS EN 61000-4-8:1994
+ A1:2001 +
BS EN 6100-4-11:2004
30A rms/m, 50Hz and 60Hz Not Applicable
Immunity to Conducted Common Mode
Disturbance, 0 to 150
kHz
BS EN 61000-4-16:1998
+ A1:2004
DC & I/O Ports:
1 to 10V rms increasing at
20dB/decade from 1,5KHz to
15k Hz:
10V rms from 15k Hz to
150k Hz
100V rms for 1s at 16.6Hz,
50Hz and 60Hz 10V rms
continuous at 150Hz and
180Hz
None
Voltage Dips, Short Interruptions and Voltage Variations for DC Input Power
Ports
BS EN 61000-4-29:2001
40% for 10ms
0% for 20ms
The performance criteria for these
tests is fail-safe
Immunity to Electrostatic Discharge
Standards
Conditions
Notes
Tested to IEC 61000-
4-2
Air discharge ± 8 kV
Contact discharge ± 6 kV
None
If the anticipated EMI exceeds these levels, additional protection measures
such as a suitably screened and Earthed enclosure shall be applied.