Field Loop Circuit for Line Monitored Digital Input for Emergency Shutdown Systems (ESD)
The suggested values for R1 and R2 are as follows:
R1 = 15K 1%, 1W (maximum power dissipated is 47mW at 26.4V)
R2 = 3K9 1%, 1W (maximum power dissipated is 182mW at 26.4V)
Suggested threshold values for both of the above circuits are as follows:
Threshold ID
Value (mV)
Maximum Allowed
=
32000
SHORT CIRCUIT
Threshold 8
=
19000
Threshold 7
=
18500
ON (nominal 16V)
Threshold 6
=
11000
Threshold 5
=
10500
INDETERMINATE
Threshold 4
=
6500
Threshold 3
=
6000
OFF (nominal 8V)
Threshold 2
=
3500
Threshold 1
=
3000
OPEN CIRCUIT
Assumptions:
Loop supply voltage = 24V ± 10%
Maximum Field Cable Line Resistance: < 100
total; this means < 50 + 50
for the two cables.