Safety Manual (AADvance Controller)


Planned Certified Configurations

Table 10:

Central Modules

Modules

TÜV Certified
Configuration

Conditions

Processor Module
T9110

1oo1D, 1oo2D,
2oo3D

Safety-related and can be used for safety-critical
applications in SIL2 with 1 module fitted and SIL3

applications with 2 or 3 modules fitted.

Note: For High Demand applications you must use

a minimum of two processors.

Table 11:

Input Modules

Modules

TÜV Certified
Configuration

Conditions

Digital Inputs
T9401/2, 24V dc,
8/16 Channel,

isolated.

+

T9801/2/3 Digital

Input TA, 16 channel,
Simplex/Dual/TMR

1oo1D, 1oo2D,
2oo3D

De-energized to action (normally energized): SIL3
with 1, 2 or 3 modules fitted.

Energize to action (normally de-energized): with 1, 2

or 3 modules fitted

Note: when the integrity level is at 1oo1D then the
faulty module must be replaced to restore the

integrity level back to 1oo2D.

Analogue Inputs

T9431/2, 8/16
Channel, isolated

+

T9831/2/3 Analogue
Input TA, 16
Channel,

Simplex/Dual/TMR

1oo1D, 1oo2D,

2oo3D

Within the manufactures specified safety accuracy

limits of 1%. The safety state of the analogue input
has to be set to a safe value which is a calculated
value based on a count value of 0mA. (refer to the

AADvance Configuration Guide Doc no: 553633 for
more details)

SIL3 with 1, 2 or 3 modules fitted.

Note: when the integrity level is at 1oo1D then the
faulty module must be replaced within the MTTR
assumed for the PFD calculations to restore the

integrity level back to 1oo2D.