Field configurations – Rockwell Automation AADvance Controller Safety Manual User Manual
Page 68

4-12
Document: 553630
ICSTT-RM446K-EN-P Issue: 10
_C
Safety Manual (AADvance Controller)
Field Configurations
The following are recommended field loop circuits for line monitoring of
digital/analogue inputs.
Use cable monitoring and circuit integrity cable as appropriate for the
application, as inter-channel short circuits cannot be detected by an AADvance
controller.
Line Monitoring
This section provides recommended line monitoring circuits and resistor
values. You can set-up line monitoring on the following modules:
T9401 and T9402 Digital Input Modules
T9431 and T9432 Analogue Input Modules
Note: You must ensure that there is no crossover between channels.
Digital Input Field Loop Circuits
Recommended Field Loop Circuits
This section contains recommended field loop circuits for line monitoring
digital inputs used in Emergency Shutdown or Fire & Gas applications.
Field Loop Circuit for Digital Input