2 polarity and phase sequence – Rockwell Automation Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control User Manual

Page 12

Advertising
background image

Publication SGI-1.1 - August 2009

12

Section 3: Application Guidelines

Programmers of PC systems should evaluate functional and safety

implications of all control paths and provide appropriate feedback

arrangements as needed.

In an electromechanical implementation of a ladder diagram, power is

available to every rung at all times, so that the logic of the various rungs is

executed continually and simultaneously, limited of course by the

operating delays inherent in the electromechanical devices. By contrast, a

typical PC examines the status of input devices (I/O scan), then executes

the user program in sequence (program scan), then changes outputs

accordingly in the next I/O scan. Therefore, the sequential order of a PC

program can be of more importance and significance than in its

electromechanical counterpart, particularly when special instructions such

as "immediate" inputs or outputs are programmed as some PC’s permit.

Also, differences in response characteristics of components, differences in

system architecture, and the scan time associates with a PC system can

combine to change timing characteristics of a circuit significantly. In

particular, care must be taken in handling momentary or rapidly changing

inputs to a PC system which might be missed between scans. Simple

transfer of a ladder diagram without consideration of these characteristics

of PC’s may produce unintended and possibly hazardous results.

Programmers should consult the user's manual in order to understand the

characteristics of the particular PC being used, and provide appropriate

features in the program to accommodate them.

Another concern is the operating mode of devices connected to input

terminals. Input signals must be arranged so loss of signal due to a broken

wire or corroded contact does not go undetected and create a hazardous

condition. In particular, stop functions should be initiated by opening a

normally closed external circuit rather than closing a normally open circuit

even though the system is capable of being programmed to accept either

type of input.

The considerations described in this section apply to the creation of "new"

programs as well as conversion of existing ladder diagrams.

3.3.2 Polarity and Phase Sequence

Input power and control signals should be applied with polarity and phase
sequence as specified by the manufacturer. Solid-state devices can be damaged
by the application of reverse polarity or incorrect phase sequence.

Comments: 3.3.2 —Polarity and Phase Sequence

Additionally, incorrect polarity or phase sequence connection may cause

erratic response by solid-state controls, with potential hazards to

personnel. Frequently, such a system contains a detection circuit that

illuminates an indicator when incorrect phase sequence is applied. Phase

sequence may be corrected by interchanging any two system input power

leads. It is advisable to check rotation of motors whenever input power

leads are disconnected and reconnected in a system.

Advertising