Section 3: Application Guidelines

17

Comments: 3.6.1 — Temperature

Operation above the maximum rated temperature will usually result in

many failures in a short time. Nuisance type malfunctions can also be

encountered as a result of elevated ambient temperature. These

malfunctions, when they occur, are usually temporary and normal

operation resumes when temperatures are lowered.

Some solid-state devices temporarily cease to function when ambient

temperature is below their minimum rated operating temperature.

Operation in cold environments should be avoided or heaters should be

installed in the equipment enclosures to bring the system up to the

minimum specified operating temperature before applying power to the

system.

Air circulating in a non-ventilated enclosure with equipment operating will

be at a higher temperature than the room in which it is installed. A

temperature differential of 10...20º C can be expected in a typical industrial

installation. See also section 2.1.

3.6.2 Contaminants

Moisture, corrosive gases and liquids, and conductive dust can all have adverse
effects on a system that is not adequately protected against atmospheric
contaminants.

If these contaminants are allowed to collect on printed circuit boards, bridging
between the conductors may result in malfunction of the circuit. This could
lead to noisy, erratic control operation, or at worst, a permanent malfunction.
A thick coating of dust could also prevent adequate cooling on the board or
heat sink, causing malfunction. A dust coating on heat sinks reduces their
thermal efficiency.

Preventive measures include a specially conditioned room or a properly
specified enclosure for the system.

Comments: 3.6.2 — Contaminants

Modules for solid-state systems usually consist of electronic devices

mounted on printed circuit boards with relatively close spacing between

conductors. Moisture in the form of humidity is one of the atmospheric

contaminants which can cause failure. If moisture is allowed to condense

on a printed circuit board, the board metallizations could "electroplate"

across the conductor spacings when voltage is applied. In low-impedance

circuits, this conductive path would immediately burn open, then reform

to be burned open again. This action can lead to erratic operation. In high

impedance circuits, a short circuit may appear resulting in a permanent

malfunction. Specifications for equipment often include a relative

humidity exposure limit, but appropriate precautions should be taken to

prevent condensation. Failures due to moisture are often accelerated in the

presence of corrosive gases or vapors. These increase the conductivity of

the moisture layer allowing electromigration to occur more rapidly and at

lower potentials.