3 off-state current – Rockwell Automation Safety Guidelines for the Application, Installation, and Maintenance of Solid-State Control User Manual

Page 5

Advertising
background image

Publication SGI-1.1 - August 2009

Section 2: General Authorized Engineering Information

5

Comments: 2.2 —Electrical Noise

Solid-state devices are generally more susceptible to electrical noise

interference than their electromechanical counterparts. The reasons are

straightforward. The operating mechanism for electromechanical devices

requires a deliberate input of electrical energy that can be converted into a

sustained mechanical force that is strong enough to close the hard

contacts and maintain the closure for the duration on the ON cycle. Most

random electrical noise signals lack the energy content to produce that

magnitude of mechanical force. The operating mechanism for solid-state

devices is totally different. The deliberate electric energy input is used to

disturb the placement of the electrically charged particles within the

molecular structure. This molecular displacement changes the electrical

characteristic from that of an insulator to that of a conductor or vice versa.

The required energy level is very low. In addition, a sustained signal is not

required for components such as SCRs, triacs, and logic gates because

these types are self-latching. Most random electrical noise signals are of

the momentary low-energy type. Since it is difficult to separate deliberate

signals from random noise, the devices are thereby more susceptible. This

is cause for special concern regarding the electrical environment and

possible need for noise rejection measures. See sections 3.4, 3.4.1, 3.4.2,

and 3.4.3.

2.3 Off-State Current

Solid-state controls generally exhibit a small amount of current flow when in
the off-state condition. Precautions must be exercised to ensure proper circuit
performance and personnel safety. The value of this current is available from
the manufacturer.

Comments: 2.3— Off-State Current

Off-state current is also referred to as leakage current in the literature. A

solid-state “contact” is a solid block of material that is switched from ON

to OFF by a change internally from a conductor to an insulator. Since a

perfect insulator does not exist, there is always some leakage current

present as long as voltage is applied to the device. The presence of leakage

current indicates that OFF does not mean OPEN. The reader is warned

that simply turning a solid-state device OFF does not remove the

possibility of a shock hazard. Solid-state and electromechanical devices

used as inputs to solid-state controls must be compatible with the

solid-state equipment with which they are used. Solid-state devices have

inherent off-state current, as explained in the preceding paragraph.

Electromechanical devices may also permit a small amount of current to

flow when the device is in the “open” position due to poor insulation

characteristics, which may be subject to further deterioration with age and

use. An example is a switching device that employs a carbon brush in

contact with an insulating segment of the switch in the off-state, such that

a conductive film may be deposited by the brush on the insulating

segment. Any input device that could produce an erroneous signal of

sufficient magnitude to cause a malfunction of the solid-state equipment,

such as unintended turn ON or inability to turn OFF, should not be used

with solid-state controls.

See also section 3.5.2.

Advertising