Banner U-GAGE T30U—Level Control User Manual

Page 4

Advertising
background image

Program Second Output

Repeat as needed for other output.

Teaching Identical (Complementary) Window Limits for Both Outputs

A Single Pair of Sensing Window Limits

is taught; only one output is on at any time

Dead Zone

Sensing

Range

Limits for

Both Outputs

1 and 2

Liquid levels here energize Output 2

Liquid levels here

energize Output 1

Figure 4. Programming one pair of sensing window limits, com-

plementary outputs

Only one output conducts at any time in response to the target distance. Under no conditions will
both outputs conduct at the same time; see

Overview

on page 1 and the figure on the left.

The distance between the taught near and far limits must be at least 10 mm in this complementa-
ry mode for proper sensor operation.

Push Button

Remote Wire

0.04 sec. < T < 0.8 sec.

Procedure

Result

Procedure

Result

Programming Mode

• Press and hold both push but-

tons (or press and hold one and
then the other)

3

>2 sec.

• Green Power LED turns OFF
• Both Output LEDs turn ON Yellow
• Sensor waits for first limit

• No action required

Teach First Limit

• Position the target for the first

limit

• “Click” either push button

• After a short delay, the Yellow

LEDs flashes

• Sensor learns first limit and waits

for second limit

• Position the target for the first limit
• Triple-pulse the remote line

T

T

T

T

T

• Green Power LED turns OFF
• Both Output LEDs turn ON Yellow
• After a short delay, the Yellow LEDs

flash

Teach Second Limit

• Position the target for the sec-

ond limit

• “Click” either push button

• After a short delay, the Green

Power LED goes ON

• Sensor learns second limit and re-

turns automatically to Run mode

• Position the target for the second limit
• Single-pulse the remote line

T

• After a short delay, the Green Power

LED turns ON

• Sensor learns second limit and re-

turns automatically to Run mode

3

Sensor will return to RUN mode if first TEACH condition is not registered within 120 seconds.

U-GAGE® T30U Series Sensors - Pump-In/Pump-Out

4

www.bannerengineering.com - tel: 763-544-3164

P/N 063974 Rev. C

Advertising