Push button lockout, Run mode, Self-diagnostic error mode – Banner U-GAGE T30U—Level Control User Manual

Page 5: Specifications

Advertising
background image

Push Button Lockout

Push Button

Remote Wire

0.04 sec. < T < 0.8 sec.

Procedure

Result

Procedure

Result

Not available via push but-
ton

Not applicable

• Four-pulse the remote line

T

T

T

T

• Push buttons are either enabled or disabled,

depending on previous condition

Run Mode

NOTE: All LED indicators momentarily turn OFF when sensor changes state between Program and Run modes.

Signal LED
The Red Signal LED indicates the strength and condition of the sensor’s incoming signal.

Signal LED Status

Indicates

OFF

No signal is received, or the target is beyond the range limitations of the sensor (with some tolerance beyond the recommen-
ded minimum and maximum sensing distance)

Flashing

Relative received signal strength; the faster the LED flashes, the stronger the signal

Output LEDs
Each Yellow Output LED lights when the corresponding output (pump-in or pump-out) is energized.
Power ON/OFF LED
The Green Power ON/OFF LED indicates the operating status of the sensor.

Power ON/OFF LED

Indicates

OFF

Power is OFF (or in Program mode, if other LEDs are ON)

ON Solid

Sensor is operating normally (power is ON, Run mode)

Flashing

Discrete output is overloaded (Run mode)

Self-Diagnostic Error Mode

In the unlikely event of a microprocessor memory error, all of the LEDs will flash in sequence. If this occurs, the setup parameters have been lost and the sensor may be
corrupt. Contact Banner Engineering for further information.

Specifications

Proximity Mode Range

“A” suffix models: 150 mm (5.9 in) min. near limit; 1 m (39 in) max. far
limit
“B” suffix models: 300 mm (11.8 in) min. near limit; 2 m (79 in) max.
far limit

Supply Voltage

12 to 24V dc (10% max. ripple) at 90 mA, exclusive of load

Supply Protection Circuitry

Protected against reverse polarity and transient voltages

Output Ratings

Dual Discrete Outputs: 100 mA maximum, total – both outputs

OFF-state leakage current: less than 10 microamps
ON-state saturation voltage: less than 1V at 10 mA and less than
1.5V at 100 mA

Output Configurations

SPST solid-state switch; choose NPN (current sinking) or PNP (current
sourcing) models

Adjustments

Sensing window limits: TEACH-mode programming of near and far
window limits may be set using membrane push buttons on sensor or
remotely via TEACH input. Window limits may be programmed separate-
ly, or together

Construction

Molded reinforced thermoplastic polyester housing

Environmental Rating

Leakproof design is rated IEC IP67, NEMA 6P

Connections

2 m (6.5 ft) or 9 m (30 ft) 5-conductor PVC-covered attached cable, or 5-
pin Euro-style quick-disconnect fitting

Operating Conditions

Temperature: −20° to +70° C (−4° to +158° F)
Humidity: 100% maximum relative humidity

U-GAGE® T30U Series Sensors - Pump-In/Pump-Out

P/N 063974 Rev. C

www.bannerengineering.com - tel: 763-544-3164