M-GAGE™ Gateway I/O Mapping

The M-GAGE Gateways are pre-programmed to allow the Gateway's inputs to set the baseline of up to six M-GAGE FlexPower Nodes.
For example, Discrete IN 1 on the Gateway triggers a baseline reading for M-GAGE FlexPower Node 1 (Device ID 1). The Gateway's
inputs 1 through 6 are mapped to Node Device IDs 1 through 6.

The M-GAGE inputs for each FlexPower Node are likewise mapped to the Gateway's discrete outputs by Device ID. M-GAGE Node
Device ID 2 is mapped to the Gateway's Discrete OUT 2. The Gateway's outputs are activated when the M-GAGE sensor is above the
established threshold value.

Use the DX80 User Configuration Tool (UCT) to adjust the M-GAGE sensor parameters.

I/O

Terminal Label

M-GAGE Gateway

M-GAGE Node

I/O

1

DI1

Discrete IN 1

to

M-GAGE Node 1 Baseline

14

2

DI2

Discrete IN 2

to

M-GAGE Node 2 Baseline

14

3

DI3

Discrete IN 3

to

M-GAGE Node 3 Baseline

14

4

DI4

Discrete IN 4

to

M-GAGE Node 4 Baseline

14

5

DI5

Discrete IN 5

to

M-GAGE Node 5 Baseline

14

6

DI5

Discrete IN 6

to

M-GAGE Node 6 Baseline

14

9

DO1

Discrete OUT 1

from

M-GAGE Node 1 M-GAGE Input

1

10

DO2

Discrete OUT 2

from

M-GAGE Node 2 M-GAGE Input

1

11

DO3

Discrete OUT 3

from

M-GAGE Node 3 M-GAGE Input

1

12

DO4

Discrete OUT 4

from

M-GAGE Node 4 M-GAGE Input

1

13

DO5

Discrete OUT 5

from

M-GAGE Node 5 M-GAGE Input

1

14

DO6

Discrete OUT 6

from

M-GAGE Node 6 M-GAGE Input

1

Modbus Register Table

I/O

Modbus Holding Register

I/O Type

I/O Range

Holding Register Representa-
tion

Terminal

Block La-

bels

Gateway /

DX85

Any Node

Min.

Max.

Min. (Dec.)

Max. (Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Discrete IN 3

0

1

0

1

DI3

4

4

4 + (Node# × 16)

Discrete IN 4

0

1

0

1

DI4

5

5

5 + (Node# × 16)

Discrete IN 5

0

1

0

1

DI5

6

6

6 + (Node# × 16)

Discrete IN 6

0

1

0

1

DI6

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

9

9

9 + (Node# × 16)

Discrete OUT 1

0

1

0

1

DO1

10

10

10 + (Node# × 16)

Discrete OUT 2

0

1

0

1

DO2

11

11

11 + (Node# × 16)

Discrete OUT 3

0

1

0

1

DO3

12

12

12 + (Node# × 16)

Discrete OUT 4

0

1

0

1

DO4

SureCross DX80 Gateway for M-GAGEs