Banner SureCross DX80 Wireless Networks User Manual

Page 6

Advertising
background image

Wiring Diagram for Thermocouple Inputs

Ax+

Ax−

TC

+

Thermocouple: When wiring the thermocouple, x is the same number. For ex-
ample, a thermocouple is wired to A1+ and A1-.

Wiring Diagram for Thermistor Inputs

A4+

A4−

The thermistor at A4 is used for cold junction compensation. If the ther-
mistor is removed, all other analog temperature points will read “alarm.”
Thermistor model Number: BWA-THERMISTOR-001.

Supported Thermocouple Types

The thermocouple Node is configured, by default, to use J-type thermocouples. The following thermocouples are available by configuring
the Node.

Thermocouple

Range °F

Range °C

Type B

212 to 3,272 °F

100 to 1,800 °C

Type C

32 to 4,208 °F

0 to 2,320 °C

Type E

-58 to 1,832 °F

-50 to 1,000 °C

Type J

-292 to 1,382 °F

-180 to 750 °C

Type K

-292 to 2,282 °F

-180 to 1,250 °C

Type L

-328 to 1,652 °F

-200 to 900 °C

Type N

32 to 2,192 °F

0 to 1,200 °C

Type R

32 to 2,912 °F

0 to 1,600 °C

Type S

32 to 2,642 °F

0 to 1,450 °C

Type T

-238 to 752 °F

-150 to 400 °C

Type U

-148 to 1,112 °F

-100 to 600 °C

LED Behavior for the Nodes

After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.

LED 1

LED 2

Node Status

(flashing green)

Radio Link Ok

(flashing red)

(flashing red)

Device Error

SureCross DX80 FlexPower Thermocouple Node