Banner SureCross DX80 Wireless Networks User Manual

Page 8

Advertising
background image

Radio and General

2.4 GHz Compliance

FCC ID UE300DX80-2400 - This device complies with
FCC Part 15, Subpart C, 15.247
ETSI/EN: In accordance with EN 300 328: V1.7.1
(2006-05)
IC: 7044A-DX8024

Spread Spectrum Technology

FHSS (Frequency Hopping Spread Spectrum)

Link Timeout

Gateway: Configurable
Node: Defined by Gateway

Radio range is with the 2 dB antenna that ships with the product.
High-gain antennas are available, but the range depends on the
environment and line of sight. To determine the range of your wire-
less network, perform a Site Survey.

Interface

Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD

Wiring Access

Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector

For European applications, power the DX80 from a Limited Power
Source as defined in EN 60950-1.

Inputs and Outputs

Discrete Inputs

Rating: 3 mA max current at 30V dc
Sample Rate: 1 second
Report Rate: On change of state

Discrete Input ON Condition

PNP: Greater than 8V
NPN: Less than 0.7V

Discrete Input OFF Condition

PNP: Less than 5V
NPN: Greater than 2V or open

Thermocouple Inputs

Sample Rate: 1 second
Report Rate: 16 seconds
Accuracy: 0.1% of full scale reading + 0.8 °C
Resolution: 0.1 °C, 24-bit A/D converter

Thermistor (used for CJC)

Model: BWA-THERMISTOR-001
Accuracy: 0.4 °C (10 to 50 °C); Up to 0.8 °C (−40 to
+85 °C)
Resolution: 0.1 °C, 24-bit A/D converter

Discrete Outputs

Update Rate: 1 second
ON Condition: Less than 0.7V
OFF Condition: Open
Output State Following Timeout: OFF

Discrete Output Rating (NMOS)

Less than 10 mA max current at 30V dc
ON-State Saturation: Less than 0.7V at 20 mA

Environmental

Ratings

DX80 models:IEC IP67; NEMA 6; (See UL section be-
low for any applicable UL specifications)
DX80...C models: IEC IP20; NEMA 1 (In a suitable en-
closure: Class I, Division 2, Group A, B, C, D; T4 −40
to 80 °C)

Operating Environment

Operating Temperature: −40 to +85 °C (Electronics);
−20 to +80 °C (LCD)
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)

Shock and Vibration

IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz

Refer to the

SureCross DX80 Wireless I/O Network Product Man-

ual

(p/n 132607) for installation and waterproofing instructions. Op-

erating the devices at the maximum operating conditions for exten-
ded periods can shorten the life of the device.

SureCross DX80 FlexPower Thermocouple Node

8

www.bannerengineering.com - tel: 763-544-3164

P/N 131297 Rev. I

Advertising