Wiring Diagrams for Analog Inputs

Connecting dc power to the communication pins will cause permanent damage. Do not exceed analog input ratings for analog inputs.
Only connect sensor outputs to analog inputs.

Analog Input Wiring (10 to 30V dc Pow-
er)

Analog Input Wiring (Externally Powered
Sensors)

Analog Input Wiring (Switch Powered
Sensors)

AIx

PWR

SureCross Device

SureCross Device

dc common

external
power

AIx or Ax+

GND

SureCross Device

AIx or A x+

SPx

(Only possible in models with switch power
(SPx) outputs)

Wiring Diagrams for Analog Outputs

Connecting dc power to the communication pins will cause permanent damage. Do not exceed analog input ratings for analog inputs.
Only connect sensor outputs to analog inputs.

Analog Output Wiring

AOx

PWR

GND

SureCross Device

Modbus Register Table

I/O

Modbus Holding Register

I/O Type

Units

I/O Range

Holding Register
Representation

Terminal

Block La-

bels

Gateway

or DX85

Any Node

Min. Val-
ue

Max.
Value

Min.
(Dec.)

Max.
(Dec.)

1

1

1 + (Node# × 16)

Discrete IN 1

-

0

1

0

1

DI1

2

2

2 + (Node# × 16)

Discrete IN 2

-

0

1

0

1

DI2

3

3

3 + (Node# × 16)

Discrete IN 3

-

0

1

0

1

DI3

4

4

4 + (Node# × 16)

Discrete IN 4

-

0

1

0

1

DI4

5

5

5 + (Node# × 16)

Analog IN 1

mA
V

0.0
0.0

20.0
10.0

0

65535

AI1

6

6

6 + (Node# × 16)

Analog IN 2

mA
V

0.0
0.0

20.0
10.0

0

65535

AI2

7

7

7 + (Node# × 16)

Reserved

8

8

8 + (Node# × 16)

Device Message

SureCross DX85 Modbus RTU Remote I/O Device

P/N 131629 rev. G

www.bannerengineering.com - tel: 763-544-3164

5