Specifications – Banner SureCross DX85 Expandable Remote I/O User Manual

Page 8

Advertising
background image

Specifications

General

Power*

Requirements: +10 to 30V dc (For European applica-
tions: +10 to 24V dc, ± 10%). (See UL section below
for any applicable UL specifications)
Consumption: Less than 1.4 W (60 mA) at 24V dc

Housing

Polycarbonate
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 in·lbf)

Interface

Indicators: Two bi-color LEDs

Wiring Access

Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector

* For European applications, power the DX80 from a Limited Pow-
er Source as defined in EN 60950-1.

Inputs and Outputs

Discrete Inputs

Rating: 3 mA max current at 30V dc
ON Condition: Greater than 8V
OFF Condition: Less than 5V

Discrete Outputs

ON Condition: Supply minus 2V
OFF Condition: Less than 2V
Output State Following Timeout: OFF

Discrete Output Rating (PNP)

100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 μA

Analog Inputs and Outputs

Rating: 24 mA
Input Impedance: 100 Ohms
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit

To verify the analog input's impedance, use an Ohm meter to
measure the resistance between the analog input terminal (AIx)
and the ground (GND) terminal.

Communication

Hardware (RS-485)

Interface: 2-wire half-duplex RS-485
Baud Rates: 9.6k, 19.2k (default), or 38.4k
Data Format: 8 data bits, no parity, 1 stop bit

Environmental

Rating

Rating for DX85 models:IEC IP67; NEMA 6; (See UL
section below for any applicable UL specifications)
Rating for DX85...C models: IEC IP20; NEMA 1 (In a
suitable enclosure: Class I, Division 2, Group A, B, C,
D; T4 −40 to 80° C)
Operating Temperature: −40 to +85° C (Electronics);
−20 to +80° C (LCD)
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)

Shock and Vibration

IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz

Refer to the SureCross™ DX80 Wireless I/O Network product manual, Banner p/n 132607, for installation and waterproofing instructions.
Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.

SureCross DX85 Modbus RTU Remote I/O Device

8

www.bannerengineering.com - tel: 763-544-3164

P/N 131629 rev. G

Advertising