Banner SureCross DX85 Expandable Remote I/O User Manual

Page 6

Advertising
background image

3. Gently unplug the ribbon cable from the board mounted into the bottom housing. For integrated battery models (no ribbon cable) and

Class I, Division 2 certified devices (ribbon cable is glued down), skip this step.

4. Remove the black cover plate from the bottom of the device's cover.

The DIP switches are located behind the rotary dials. After making the neces-
sary changes to the DIP switches, place the black cover plate back into posi-
tion and gently push into place. Plug the ribbon cable in after verifying that
the blocked hole lines up with the missing pin. Mount the cover back onto the
housing.

DIP Switch Settings for a DX85

Use the DIP switches 1 through 4 on the board to set the baud rate and parity and DIP switch 5 to set the rotary dial mode.

DIP Switches

1

2

3

4

5

Baud Rate: 19200

OFF*

OFF*

Baud Rate: 38400

OFF

ON

Baud Rate: 9600

ON

OFF

Baud Rate: 19200

ON

ON

Parity: None

OFF*

OFF*

Parity: Even

OFF

ON

Parity: Odd

ON

OFF

Parity: None

ON

ON

Rotary Dial Decimal Mode

OFF*

Rotary Dial Hex Mode

ON

* Default configuration

Verify Communications on the DX85 Modbus RTU Remote I/O

After powering up, verify the DX85 is communicating properly. LED 1 should be on and green.

Status

LED 1

LED 2

Power ON

Green ON

-

Device error, contact factory

Red flashing

Red flashing

Modbus communication ac-
tive

-

Yellow flashing

Modbus communication error

-

Red flashing

The Modbus communication LEDs refer to the communication between the DX85 and what it is connected to (host system, Gateway,
Data Radio, etc).

SureCross DX85 Modbus RTU Remote I/O Device

6

www.bannerengineering.com - tel: 763-544-3164

P/N 131599 rev. G