U-gage, T30 series with analog and discrete outputs, Run mode – Banner U-GAGE T30U—Level Control User Manual

Page 5: Analog output, Self-diagnostic error mode

Advertising
background image

U-GAGE

T30 Series with Analog and Discrete Outputs

P/N 57438 Rev. C

5

Banner Engineering Corp.

Minneapolis, MN U.S.A.

www.bannerengineering.com • Tel: 763.544.3164

RUN Mode

NOTE: All LED indicators momentarily go OFF when sensor changes state between

PROGRAM and RUN modes.

Signal LED
The red Signal LED indicates the strength and condition of the sensor’s incoming
signal.

Signal LED Status

Indicates

OFF

No signal is received, or the target is beyond the range limitations
of the sensor (with some tolerance beyond the recommended
minimum and maximum sensing distance)

Flashing

Relative received signal strength

Power ON/OFF LED

Indicates

OFF

Power is OFF (or in PROGRAM mode, if other LEDs are ON)

ON Solid

Sensor is operating normally (power is ON, RUN mode)

Output LEDs
Each yellow Output LED lights when a target is sensed within the programmed window
limits.

Power ON/OFF LED
The green Power ON/OFF LED indicates the operating status of the sensor.

Analog Output

The U-GAGE T30 Series sensor may be programmed for either a positive or a negative
output slope, based on which condition is taught first (see Figure 3). If the near limit is
taught first, the slope will be positive; if the far limit is taught first, the slope will be
negative. Banner’s scalable analog output automatically distributes the output signal over
the width of the programmed sensing window.

The U-GAGE T30 also features a 2-second hold upon loss of the analog signal, which is
useful for harsh and unstable applications. In the event of analog signal loss for longer
than 2 seconds, the analog output goes to 3.6 mA or 0V dc, which may be used to trigger
an alarm.

Self-Diagnostic Error Mode

In the unlikely event of a microprocessor memory error, all of the LEDs will flash in
sequence. If this occurs, the setup parameters have been lost and the sensor may be
corrupt. Contact your Banner representative for further information.

0

Near

Window

Far

Window

10

Target Position

Analog Output (V dc)

Positive

Slope

Voltage-Sourcing Models

Figure 3.

Output current as a function of
target position

NOTE: The analog current output tracks

slightly past each window limit

(from 3.8 to 20.5 mA).

4

Near

Window

Far

Window

20

Target Position

Analog Output (mA)

Positive

Slope

Current-Sourcing Models

Flashing

Discrete output is overloaded (RUN mode)