Wiring Diagrams

5-pin Euro-Style Hookup

Wiring the 5-pin Euro-style connector depends on the model and power requirements of the device. Connecting dc power to the commu-
nication pins will cause permanent damage.

Wire No.

Wire Color

Description

1

Brown

10 to 30V dc

2

White

RS485 / D1 / B / +

3

Blue

dc common (GND)

4

Black

RS485 / D0 / A / –

5

Gray

Comms Gnd

Terminal Block (IP67 Housing)

When your wireless network does not include a host system, the eight input/four output Gateway must be mapped to the four input/eight
output Node. Connecting dc power to the communication pins will cause permanent damage.

PWR

GND

PWR

GND

DO4

DO3

DO2

DO1

DI8

DI7

DI6

DI5

DI4

DI3

DI2

DI1

DIx. Discrete IN x.
DOx. Discrete OUT x.
GND. Ground/dc common connection.
PWR. Power, 10 to 30V dc power connection.

DX80...C Wiring

Wiring power to the DX80...C models varies depending the power requirements of the model.

Terminal Label Gateway, DX85 *

10 to 30V dc Powered Nodes

Battery Powered Nodes **

V+

10 to 30V dc

10 to 30V dc

Tx/+

RS485 / D1 / B / +

V-

dc common (GND)

dc common (GND)

dc common (GND)

Rx/-

RS485 / D0 / A / -

B+

3.6 to 5.5V dc

* Connecting dc power to the communication pins will cause permanent damage.
** For FlexPower devices, do not apply more than 5.5V to the gray wire.

Terminal Block (IP20 Housing)

When your wireless network does not include a host system, the eight input/four output Gateway must be mapped to the four input/eight
output Node. Connecting dc power to the communication pins will cause permanent damage.