Verify Communications on the DX85 Modbus RTU Remote I/O

After powering up, verify the DX85 is communicating properly. LED 1 should be on and green.

Status

LED 1

LED 2

Power ON

Green ON

-

Device error, contact factory

Red flashing

Red flashing

Modbus communication ac-
tive

-

Yellow flashing

Modbus communication error

-

Red flashing

The Modbus communication LEDs refer to the communication between the DX85 and what it is connected to (host system, Gateway,
Data Radio, etc).

Specifications

General

Power*

Requirements: +10 to 30V dc (For European applica-
tions: +10 to 24V dc, ± 10%). (See UL section below
for any applicable UL specifications)
Consumption: Less than 1.4 W (60 mA) at 24V dc

Housing

Polycarbonate
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 in·lbf)

Interface

Indicators: Two bi-color LEDs

Wiring Access

Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector

* For European applications, power the DX80 from a Limited Pow-
er Source as defined in EN 60950-1.

Inputs and Outputs

Discrete Inputs

Rating: 3 mA max current at 30V dc
ON Condition: Greater than 8V
OFF Condition: Less than 5V

Discrete Outputs

ON Condition: Supply minus 2V
OFF Condition: Less than 2V

Discrete Output Rating (PNP)

100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 μA

Communication

Hardware (RS-485)

Interface: 2-wire half-duplex RS-485
Baud Rates: 9.6k, 19.2k (default), or 38.4k
Data Format: 8 data bits, no parity, 1 stop bit

Environmental

Environmental

Shock and Vibration

IEC 68-2-6 and IEC 68-2-7

SureCross DX85 Modbus RTU Remote I/O Device

P/N 134324 rev. F

www.bannerengineering.com - tel: 763-544-3164

7