Set Temp Menu (1 of 4)

Setting

Display

SET HEAT ROOM
Set the room heating temperature for the event.

Room

Access Level: Installer, User

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Always available

Default: 70°F (21.0°C)

SET HEAT ROOM
Set the room heating temperature for the event.

Room

Access Level: Installer, User

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Schedules are in use or Scenes are
set to All or Guest.

Default: 65°F (18.5°C)

SET HEAT ROOM AWAY
Set the room heating temperature for the Away
scene.

Room

Access Level: Installer, User

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Scenes is set to Away, All or Guest.

Default: 62°F (16.5°C)

HEAT MINIMUM ROOM LIMIT
Set the minimum room heating limit.

Access Level: Installer

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Schedules are in use or Scenes are
set to All or Guest.

Default: 40°F (4.5°C)

HEAT MAXIMUM ROOM LIMIT
Set the maximum room heating limit for the
event.
Access Level: Installer

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Always available

Default: 85°F (29.5°C)

HEAT MAXIMUM ROOM LIMIT
Set the maximum room heating limit for the
event.
Access Level: Installer

Range: 40 to 95°F (4.5 to 35.0°C)

Conditions: Schedules are in use or Scenes are
set to All or Guest.

Default: 85°F (29.5°C)

WARM WEATHER SHUT DOWN
Set the outdoor air temperature at which heating is
suspended during the event.

Access Level: Installer

Range: CTRL (control), 40 to
100°F (4.5 to 38.0°C), OFF

Conditions: An outdoor sensor must be available.

Default: CTRL