Sequence of operation, Heating operation, Heat pump - heating mode – tekmar 557 Thermostat Installation User Manual

Page 33: Set heat temperature, Air temperature heating, Floor heating

Advertising
background image

© 2014

557_D - 09/14

33 of 52

A Watts Water Technologies Company

Heating Operation

Section A

Sequence of Operation

Set Heat Temperature

-----------------------------------------------

-----------------------------------------------

The 557 can operate radiant floor heating, heat pump stage 1 and stage 2, and a backup
heat source to provide heating in different combinations depending on the outdoor air
temperature. The illustration below shows when each of the available heating units are
available. The “Heat On” symbol is shown on the display when the thermostat is heating. If not
operating a heat pump, the first and second stage of heat (W1 and W2) are allowed to turn
on below the Warm Weather Shut Down to maintain the Set Heat Room temperature.

No heating

Air heating only

All allowed

No backup heat

Colder

Outdoor

Temperature

Set Heat

Room

Room

Warmer

Room

Colder

Warm Weather

Shut Down

Default = 70°F

Radiant Floor

Warm Weather

Shut Down

Default = 60°F

Balance

Point

Default = Off

Lockout

Default = 60°F

Heat Pump - Heating Mode

No heat pump

Y2 off

Y1 off

Y2 on

Y1 on

W2 off

Y2 off

Y1 off

W1 off

W2 on

Y2 on

Y1 on

W1 on

Y2 off

Y1 off

W1 off

Y2 on

Y1 on

W1 on

W2 off

W1 off

W2 on

W1 on

Air Temperature Heating

---------------------------------------------

---------------------------------------------

When using only a room temperature sensor, the thermostat operates the heating
system to maintain the Set Heat Room temperature.

Floor Heating

--------------------------------------------------------

--------------------------------------------------------

When using both a room and a floor temperature sensor, the thermostat always maintains
the Floor Minimum temperature, even when the air temperature is satisfied. When the
air temperature is below the Set Heat Room temperature, the thermostat operates the
heating system to maintain the Set Heat Room temperature. The floor is never heated
above the Floor Maximum setting in order to protect the floor covering.

Suggested Floor Maximum settings are 90°F (32°C) for tile, stone, or concrete floors
and 85°F (29°C) for wood floors.