tekmar 557 Thermostat Installation User Manual

Page 21

Advertising
background image

© 2014

557_D - 09/14

21 of 52

A Watts Water Technologies Company

Setting

Display

ROOM HIGH
The highest recorded room temperature measurement.
Touch the number and the ENTER key to reset.

Access Level: Installer, User

Range: -76 to 149°F
(-60.0 to 65.0°C)

Conditions: Setup setting Room Sensor is set to ON
or Sensor 1, 2 or 3 is set to ROOM.

Default: Not applicable.

ROOM LOW
The lowest recorded room temperature measurement.
Touch the number and the ENTER key to reset.

Access Level: Installer, User

Range: -76 to 149°F
(-60.0 to 65.0°C)

Conditions: Setup setting Room Sensor is set to ON
or Sensor 1, 2 or 3 is set to ROOM.

Default: Not applicable.

FLOOR HIGH
The highest recorded floor temperature measurement.
Touch the number and the ENTER key to reset.

Access Level: Installer, User

Range: -76 to 149°F
(-60.0 to 65.0°C)

Conditions: Setup menu setting Sensor 1, 2 or 3 is
set to FLOR.

Default: Not applicable.

FLOOR LOW
The lowest recorded floor temperature measurement.
Touch the number and the ENTER key to reset.

Access Level: Installer, User

Range: -76 to 149°F
(-60.0 to 65.0°C)

Conditions: Setup menu setting Sensor 1, 2 or 3 is
set to FLOR.

Default: Not applicable.

FILTER HOURS
The total number of hours the fan has been operating
since the air filter was last replaced. Touch the number
and the ENTER key to reset and clear the Change
Filter warning message.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Always available.

Default: 0000 hours

HEAT Y1 HOURS
The total number of hours the first stage of heat pump
has been in heating operation. Touch the number
and the ENTER key to reset.
Access Level: Installer, User

Range: 0000 to 9999 hours

Conditions: Setup menu setting Y1 TYPE is set to
HP1.

Default: 0000 hours

Monitor Menu (3 of 5)