Error Message

Description

SETUP MENU SAVE ERROR
The thermostat failed to read the Setup menu settings from memory
and has reloaded the factory default settings. The thermostat stops
normal operation until all settings in the Setup menu are checked
except to provide freeze protection. To clear the error, set the access
level to Installer and check all settings in the Setup menu.

SET TEMP MENU SAVE ERROR
The thermostat failed to read the Set Temp menu settings from memory
and has reloaded the factory default settings. The thermostat stops
normal operation until all settings in the Set Temp menu are checked
except to provide freeze protection. To clear the error, set the access
level to Installer and check all settings in the Set Temp menu.

MONITOR MENU SAVE ERROR
The thermostat failed to read the Monitor menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Monitor menu.

SCHEDULE MENU SAVE ERROR
The thermostat failed to read the Schedule menu settings from
memory and has reloaded the factory default settings. The thermostat
continues to operate normally while displaying this error. To clear the
error, set the access level to Installer and check all settings in the
Schedule menu.

TOOLBOX MENU SAVE ERROR
The thermostat failed to read the Toolbox menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Toolbox menu.

TIME MENU SAVE ERROR
The thermostat failed to read the Time menu settings from memory and
has reloaded the factory default settings. The thermostat continues to
operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Time menu.

SCENES MENU SAVE ERROR
The thermostat failed to read the Scenes menu settings from memory
and has reloaded the factory default settings. The thermostat continues
to operate normally while displaying this error. To clear the error, set the
access level to Installer and check all settings in the Scenes menu.