Setting

Display

Y2 RELAY
Select the equipment the Y2 relay operates.
HP2 = Second stage heat pump
AC2 = Second stage air conditioner
HRV = Heat recovery ventilator
DHUM = Dehumidifier
VALV = Hydronic valve for building loop

Access Level: Installer

Range: OFF, HP2, AC2, HRV,
DHUM, VALV

Conditions: Always available.

Default: OFF

ACCESSORY RELAY
Select the equipment the accessory relay operates.
HUM = Humidifier
DHUM = Dehumidifier
VALV = Hydronic valve for building loop
Access Level: Installer

Range: OFF, HUM, DHUM, VALV

Conditions: Always available.

Default: OFF

O/B VALVE
Select the heat pump operation of the O / B relay.
O = Turn on during cooling, turn off during heating
B = Turn off during cooling, turn on during heating
Access Level: Installer

Range: O or B

Conditions: Y1 RELAY is set to HP1.

Default: O

HP SOURCE
Select the type of source for the heat pump.
AIR = Air source heat pump
GEO = Geothermal source heat pump
LOOP = Building hydronic loop heat pump
Access Level: Installer

Range: AIR, GEO, LOOP

Conditions: Y1 RELAY is set to HP1.

Default: AIR

Y MINIMUM OFF
Select the compressor minimum off time.

Access Level: Installer

Range: 0:30 to 10:00 minutes

Conditions: Always available.

Default: 5:00 minutes

Y2 DIFFERENTIAL
Select the Y2 differential on point.

Access Level: Installer

Range: 0.0 to 4.0°F (0.0 to 4.0°C)

Conditions: Y2 RELAY is set to HP2 or AC2.

Default: 0.5°F