INSTALLATION

3-4

Manual 0-2532

3.07 Voltage Selection

The Power Supply can be wired to use input voltages
from 200 - 575 VAC. Power Supply is factory-wired for
460 VAC, three-phase input. Voltage selection is accom-
plished by switching busbar connections on the input
voltage terminal board inside the Power Supply.

1. Locate the input voltage terminal board on the

left side of the power supply.

Input Voltage

Terminal Board

L1

L2

L3

Busbars

A-00985

Extra Busbar

Storage Location

Figure 3-4 Input Voltage Terminal Board Location

NOTE

Extra busbars are attached (stored) to the top
side of the power transformer assembly.

2. Check the busbar configuration on the input volt-

age terminal board . The busbar configuration
must correspond with the available line voltage
per the following figure and the label inside the
unit:

200, 208,

220, or 230

11

12

L3

13

15

14

6

7

L2

8

10

9

1

2

L1

3

5

4

380, 415,

or 460

11

12

L3

13

15

14

6

7

L2

8

10

9

1

2

L1

3

5

4

500, or 575

11

12

L3

13

15

14

6

7

L2

8

10

9

1

2

L1

3

5

4

Busbar Connections For Input Voltages

A-00904

Figure 3-5 Busbar Connections

If necessary, reposition the busbars to correspond to
the available line voltage.

3.08 Primary Power Cable

Connections

WARNING

Disconnect primary power at the source be-
fore connecting the primary power cable to
the power supply.

The primary power cable must be supplied by the end
user and installed to the Power Supply assembly. Rec-
ommended cable sizes are specified in Appendix I.

NOTE

Three-phase operation requires a 3-conduc-
tor cable with ground.

1. Route the primary power cable through the strain

relief fitting in the rear panel of the Power Supply
and tighten strain relief screws.