Table 1 -- Physical Data -- Unit 48EZ--A (Cont’d)

UNIT SIZE 48EZ ---A

48090

48115

48130

60090

60115

60130

NOMINAL CAPACITY ---ton

4

4

4

5

5

5

OPERATING WEIGHT---lb

(kg)

482

219

482

219

482

219

507

230

507

230

507

230

COMPRESSORS

Scroll

Quantity

1

REFRIGERANT (R---410A)

Quantity ---lb

(kg )

9.6

4.4

12.3

5.6

REFRIGERANT METERING DEVICE

TXV

OUTDOOR ORIFICE---in. (qty)

(mm)

0.046 (2)

1.2

0.052 (2)

1.3

OUTDOOR COIL

Rows...Fins---in.

Face Area---sq ft

2...21

13.6

2...21

13.6

2...21

13.6

2...21

17.5

2...21

17.5

2...21

17.5

OUTDOOR FAN

Nominal Cfm

Diameter---in.

(mm)

Motor Hp---Rpm

3100

26

660

1/5 (810)

3100

26

660

1/5 (810)

3100

26

660

1/5 (810)

3500

26

660

1/5 (810)

3500

26

660

1/5 (810)

3500

26

660

1/5 (810)

INDOOR COIL

Rows...Fins---in.

Face Area---sq ft

3...17

4.7

3...17

4.7

3...17

4.7

3...17

5.7

3...17

5.7

3...17

5.7

INDOOR BLOWER

Nominal Cooling Airflow---(CFM)

Size---in.

(mm)

Motor ---hp

1600

11x10

279x254

1.0

1600

11x10

279x254

1.0

1600

11x10

279x254

1.0

1850

11x10

279x254

1.0

1850

11x10

279x254

1.0

1850

11x10

279x254

1.0

FURNACE SECTION*

Burner Orifice

Natural Gas Qty...Drill Size (Factory Installed)

Propane GasQty...Drill Size

3...38

3...53

3...33

3...51

3...31

3...49

3...38

3...53

3...33

3...51

3...31

3...49

HIGH---PRESSURE SWITCH (psig) Cut---out

Reset (Auto)

650 +/---15

420 +/---25

LOSS---OF---CHARGE /

LOW---PRESSURE SWITCH

(Liquid Line) (psig)

Cut---out

Reset (auto)

20 +/---5

45 +/---10

RETURN---AIR FILTERS †

Throwaway (in.)

(mm)

24x36x1

(610x914x25)

*Based on altitude of 0 to 2000 ft (0---610 m).
{

Required filter sizes shown are based on the larger of the AHRI (Air Conditioning, Heating and Refrigeration Institute) rated cooling airflow or the heating airflow

velocity of 300 ft/minute for high---capacity type. Air filter pressure drop for non---standard filters must not exceed 0.08 IN. W.C.
}

If using accessory filter rack refer to filter rack installation instructions for correct filter size and quantity.

Table 2 – Maximum Gas Flow Capacity*

NOMINAL

IRON

PIPE,

SIZE (IN.)

INTERNAL

DIAMETER

(IN.)

LENGTH OF PIPE, FT† (m)

10

(3.1)

20

(6.1)

30

(9.1)

40

(12.2)

50

(15.2)

60

(18.3)

70

(21.3)

80

(24.4)

90

(27.4)

100

(30.5)

125

(38.1)

150

(46.0)

175

(53.3)

200

(61.0)

1/2

.622

175

120

97

82

73

66

61

57

53

50

44

40

3/4

.824

360

250

200

170

151

138

125

118

110

103

93

84

77

72

1

1.049

680

465

375

320

285

260

240

220

205

195

175

160

145

135

1---1/4

1.380

1400

950

770

600

580

530

490

460

430

400

360

325

300

280

1---1/2

1.610

2100

1460

1180

990

900

810

750

690

650

620

550

500

460

430

* Capacity of pipe in cu ft of gas per hr for gas pressure of 0.5 psig or less. Pressure drop of 0.5---IN. W.C. (based on a 0.60 specific gravity gas). Refer to Table 2

and National Fire Protection Association NFPA 54/ANSI Z223.1.

† This length includes an ordinary number of fittings.

Table 3 – Heating Inputs

HEATING INPUT

(BTUH)

NUMBER OF

GAS SUPPLY PRESSURE (IN. W.C.)

MANIFOLD PRESSURE

NUMBER OF

ORIFICES

Natural{

Propane*{

MANIFOLD PRESSURE

(IN. W.C.)

ORIFICES

Min

Max

Min

Max

Natural{

Propane*†

40,000

2

4.0

13.0

11.0

13.0

3.2∼3.8

10.0∼11.0

60,000

2

4.0

13.0

11.0

13.0

3.2∼3.8

10.0∼11.0

90,000

3

4.0

13.0

11.0

13.0

3.2∼3.8

10.0∼11.0

115,000

3

4.0

13.0

11.0

13.0

3.2∼3.8

10.0∼11.0

130,000

3

4.0

13.0

11.0

13.0

3.2∼3.8

10.0∼11.0

*

When a unit is converted to propane, different size orifices must be used. See separate, natural---to---propane conversion kit instructions.

{

Based on altitudes from sea level to 2000 ft (610 m) above sea level. In U.S.A. for altitudes above 2000 ft (610 m), reduce input rating 4 percent for each addi-

tional 1000 ft (305 m) above sea level. In Canada, from 2000 ft (610 m) above sea level to 4500 ft (1372 m) above sea level, derate the unit 10 percent.