Warning – Carrier 48EZ(N)-A User Manual

Page 35

Advertising
background image

35

OF2

OF1

ON

QUIET

SHIFT

120

30

60

60

30

90

INTER

V

AL

TIMER

OFF

P3

DFT

O R

W

2

Y C

T2 C C O

DFT

T1

Y

P1

J1

SPEEDUP

Speedup
Pins

Defrost interval
DIP switches

Quiet
Shift

A08020

Fig. 23 -- Defrost Control

EXPLOSION,

PERSONAL

INJURY

AND

ENVIRONMENTAL HAZARD
Failure to follow this warning could result in personal injury,

death or property damage.
System under pressure. Relieve pressure and recover all

refrigerant before system repair or final unit disposal. Use all

service ports and open all flow--control devices, including

solenoid valves.

!

WARNING

If oil is detected or if low cooling performance is suspected,

leak--test all refrigerant tubing using an electronic leak--detector,
halide torch, or liquid--soap solution. If a refrigerant leak is

detected, refer to the Check for Refrigerant Leaks section.
If no refrigerant leaks are found and low cooling performance is

suspected, refer to the Checking and Adjusting Refrigerant Charge
section.

Gas Input

The gas input does not require checking unless improper heating

performance is suspected. If a problem exists, refer to the Start--Up
section.

Indoor Airflow

The heating and/or cooling airflow does not require checking

unless improper performance is suspected. If a problem exists, be
sure that all supply-- and return--air grilles are open and free from

obstructions, and that the air filter is clean. When necessary, refer to

the Indoor Airflow and Airflow Adjustments section to check the
system airflow.

Check Defrost Thermostat

The defrost thermostat is usually located on the lowest liquid

leaving circuit of the left condenser coil (see Fig. 21). The
thermostat closes at 32_F (0_C) and opens at 65_F (18_C).

Puron Items
Metering Device
(Thermostatic Expansion Valve &
Piston)

This unit uses both a hard shutoff, balance port TXV in the indoor

coil and a piston in each side of the outdoor coil. The TXV

maintains a constant superheat at the evaporator coil exit (cooling
mode) resulting in higher overall system efficiency.

Pressure Switches

Pressure switches are protective devices wired into control circuit

(low voltage). They shut off compressor if abnormally high or low
pressures are present in the refrigeration circuit. These pressure

switches are specifically designed to operate with Puron (R--410A)
systems. R--22 pressure switches must not be used as replacements

for the Puron (R--410A) system.

Loss of Charge Switch

This switch is located on the liquid line and protects against low
suction pressures caused by such events as loss of charge, low

airflow across indoor coil, dirty filters, etc. It opens on a pressure
drop at about 20 psig. If system pressure is above this, switch

should be closed. To check switch:

1. Turn off all power to unit.

48E

Z

--

A

Advertising