Continuous fan operation, 48e z -- a, Fig. 13 -- interface fan board (ifb) – Carrier 48EZ(N)-A User Manual

Page 18

Advertising
background image

18

2. Remove the current speed tap wire from the “LOW”

terminal on the interface fan board (IFB) (See Fig. 13) and

place vinyl cap over the connector on the wire.

3. Connect the desired speed tap wire to the “LOW” terminal

on the interface fan board (IFB).

Two Cooling Fan Speeds Set-up (Dehumidification

feature used)

IMPORTANT: Dehumidification control must open control
circuit on humidity rise above set point.
Use of the dehumidification cooling fan speed requires use of
either a 24 VAC dehumidistat or a thermostat which includes

control of a 24 VAC dehumidistat connection. In either case, the

dehumidification control must open the control circuit on humidity
rise above the dehumidification set point.

1. Remove fan speed tap wire from the “LOW” terminal on

the interface fan board (IFB) (See Fig. 13).

2. Determine correct normal cooling fan speed for unit and

application. Add the wet coil pressure drop in Table 9 to
the system static to determine the correct cooling airflow

speed in Table 7 that will deliver the nominal cooling
airflow as listed in Table 1 for each size.

3. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 6 for color coding) for the normal cooling
fan speed and place desired speed tap wire on “HIGH” on

the interface board.

4. Refer to airflow tables (Table 7) to determine allowable

speeds for the dehumidification cooling fan speed. In Table
7, speeds that are not allowed for dehumidification cooling

are shaded.

5. Remove the vinyl cap off of the desired speed tap wire

(Refer to Table 6 for color coding) for the dehumidification

cooling fan speed and place desired speed tap wire on the
“LOW” connection on the interface board (IFB). Verify

that static pressure is in the acceptable range for the speed
tap to be used for dehumidification cooling.

6. Use any spare vinyl plugs to cap any unused speed tap

wires.

Continuous Fan Operation

When the DEHUM feature is not used, the continuous fan speed

will be the same as cooling fan speed. When the DEHUM feature
is used, the continuous fan will operate on IFB “LOW” speed

when the DH control lead is not energized, or IFB “HIGH” speed
when the DH lead is energized (see Fig. 13).
NOTE: For heat pump operation, the recommended airflow is 350
to 450 CFM for each 12,000 Btuh of rated cooling capacity.

Table 6 – Color Coding for Indoor Fan Motor Leads

Black = High Speed

Orange = Med---High Speed

Red = Med Speed

Pink = Med---Low Speed

Blue = Low Speed

COM

LOW

HIGH

GAS
HEAT

Q1

R1L

C8

RL3

Q3

DCR

QCR

QC1

G1

G2

A7

D4

D6

C2

OILL

R9

AB A15

C4

C9

C0

R4

RL4

C7

R2

R3

R5 R6

QCB

Y

Y

R

U

C 24VAC

JW1

P2

P1

W2

Y2/

Y1/

Y

DH

G

C

R

SSTZ-8

P3

SDL

24V

AC/R

CDM/C

F1

QC6

QC7

QC4

QC3

K2

K1

D2

RI0

RI2

JM6

RI

DL

JM5

U1

C3

D3

D5

JW3

JW2

JW4

JW7

3 AMP

C

A09058

Fig. 13 -- Interface Fan Board (IFB)

48E

Z

--

A

Advertising