Warning, Caution – Carrier 48EZ(N)-A User Manual

Page 9

Advertising
background image

9

Step 9 — Install Duct Connections

The unit has duct flanges on the supply-- and return--air openings
on the side and bottom of the unit. For downshot applications, the

ductwork connects to the roof curb (See Fig. 2 and 3 for

connection sizes and locations).

Configuring Units for Downflow (Vertical) Discharge

ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury

or death.
Before installing or servicing system, always turn off main

power to system and install lockout tag. There may be more

than one disconnect switch.

!

WARNING

1. Open all electrical disconnects before starting any service

work.

2. Remove horizontal (metal) duct covers to access vertical

(downflow) discharge duct knockouts in unit basepan. (See
Fig. 8.)

PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Collect ALL screws that were removed. Do not leave screws

on rooftop as permanent damage to the roof may occur.

CAUTION

!

To remove downflow return and supply knockout covers, break
front and right side connecting tabs with a screwdriver and

hammer. Push cover down to break rear and left side tabs.
NOTE: These panels are held in place with tabs similar to an
electrical knockout. Reinstall horizontal duct covers (Fig. 8)
shipped on unit from factory. Insure openings are air and
watertight.
NOTE: The design and installation of the duct system must be in
accordance with the standards of the NFPA for installation of
nonresidence--type air conditioning and ventilating systems, NFPA
90A or residence--type, NFPA 90B; and/or local codes and
ordinances.
Adhere to the following criteria when selecting, sizing, and
installing the duct system:

1. Units are shipped for horizontal duct installation (by

removing duct covers).

2. Select and size ductwork, supply--air registers, and

return--air grilles according to American Society of Heating,
Refrigeration and Air Conditioning Engineers (ASHRAE)

recommendations.

3. Use flexible transition between rigid ductwork and unit to

prevent transmission of vibration. The transition may be

screwed or bolted to duct flanges. Use suitable gaskets to
ensure weather tight and airtight seal.

4. All units must have field--supplied filters or accessory filter

rack installed in the return--air side of the unit.
Recommended sizes for filters are shown in Table 1.

5. Size all ductwork for maximum required airflow (either

heating or cooling) for unit being installed. Avoid abrupt
duct size increases or decreases or performance may be

affected.

6. Adequately insulate and weatherproof all ductwork located

outdoors. Insulate ducts passing through unconditioned
space, and use vapor barrier in accordance with latest issue
of Sheet Metal and Air Conditioning Contractors National

Association (SMACNA) and Air Conditioning Contractors
of America (ACCA) minimum installation standards for

heating and air conditioning systems. Secure all ducts to
building structure.

7. Flash, weatherproof, and vibration--isolate all openings in

building structure in accordance with local codes and good
building practices.

Horizontal Duct Covers

A09061

Basepan
Downflow
(Vertical)
Supply
Knockout

Basepan
Downflow
(Vertical)
Return
Knockout

A09060

Fig. 8 -- Supply and Return Duct Opening

48E

Z

--

A

Advertising