Annunciator module, Field adjustments, The annunciator module – Amico Valve Alarm Combo Unit User Manual

Page 12

Advertising
background image

Annunciator Module

Noise Level Control

Factory Default: 80 Decibels

To decrease noise level:

1. Locate jumper at J5. Move jumper to:

LVL1 = 90 dBa.

LVL2 = 80 dBa.

LVL3 = 70 dBa.

Control of Remote Alarm Buzzer

Factory Default: Normal Condition

To silence remote alarm buzzer when silencing the annunciator module:

1. Locate jumper at J6. Move jumper to:

NORM =

Remote alarm buzzer will silence when annunciator module is silenced.

ALRM =

Remote alarm will not silence when annunciator module is silenced.

The buzzer will only silence when an alarm condition has been cleared.

Please refer to Appendix B.

A m i c o M i c r o p r o c e s s o r B a s e d A l a r m

P a g e : 1 6

FIELD ADJUSTMENTS

THE ANNUNCIATOR MODULE

NOISE LEVEL CONTROL

Factory Default: 90 Decibles

To decrease noise level:
1.

Locate jumper at J5. Move jumper to:
LVL1 = 90 dBa.
LVL2 = 80 dBa.
LVL3 = 70 dBa.

CONTROL OF REMOTE ALARM BUZZER

Factory Default: Normal Condition

To silence remote alarm buzzer when silencing the

annunciator module:
1.

Locate jumper at J6. Move jumper to:

NORM =
Remote alarm buzzer will silence when annunciator

module is silenced.

ALRM =
Remote alarm will not silence when annunciator

module is silenced. The buzzer will only silence

when alarm condition has been cleared. Please

refer to Appendix B.

J6

TEST

ALRM

NORM

SILENCE

LVL1

LVL2

LVL3

J5

A m i c o M i c r o p r o c e s s o r B a s e d A l a r m

P a g e : 1 6

FIELD ADJUSTMENTS

THE ANNUNCIATOR MODULE

NOISE LEVEL CONTROL

Factory Default: 90 Decibles

To decrease noise level:
1.

Locate jumper at J5. Move jumper to:
LVL1 = 90 dBa.
LVL2 = 80 dBa.
LVL3 = 70 dBa.

CONTROL OF REMOTE ALARM BUZZER

Factory Default: Normal Condition

To silence remote alarm buzzer when silencing the

annunciator module:
1.

Locate jumper at J6. Move jumper to:

NORM =
Remote alarm buzzer will silence when annunciator

module is silenced.

ALRM =
Remote alarm will not silence when annunciator

module is silenced. The buzzer will only silence

when alarm condition has been cleared. Please

refer to Appendix B.

J6

TEST

ALRM

NORM

SILENCE

LVL1

LVL2

LVL3

J5

1. Turn on Alarm

2. Set switches #8 and #10 the OFF position

3. Set switches #5 and #6 the ON position

4. The display will show the current reading of the pressure

5. Adjust the calibration, using the “UP” and “DOWN” push buttons, to the desired value.

6. Set switches #5 and #6 the OFF position

7. Turn on #10 if AIMS is connected (do not turn on #8)

When you have completed step #7, the display module will automatically go into “RESET” mode. This will store

the data that you entered.

Steps to Re-Calibrate the Sensor from Area Module v4.0

12

Amico Pipeline

Advertising
This manual is related to the following products: