A dip-switch is located on the back of the display module which is used to identify the gas of the display

module. The dip-switch contains ten switch settings.

Pressure Only

Factory Default:
High = 60 Psi, Low = 40 Psi
Repeat time = 30 min.

High Pressure/Nitrogen

Factory Default:
High = 195 Psi, Low = 140 Psi
Repeat time = 30 min.

During programming, the “Trend Bar” will flash!

1. Set switch #6, #7 and #8 to the ON position.

2. The LED will display (HI-), followed by the current set point. Indicating that the system is ready

to accept a new High set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the

desired value.

3. Set switch #7 to the OFF position.

4. The LED will display (LO-), followed by the current set point. Indicating the system is ready to

accept a new Low set point. Adjust set point, using the “UP” and “DOWN” push buttons, to the

desired value.

5. Set switch #8 to the OFF position.

6. The LED will display (I-I-), followed by the current set point. Indicating the system is ready to

accept a new Repeat Time set point. Adjust set point using the “UP” and “DOWN” push buttons,

to the desired value. [(Display dd=Disabled) Range from 1 to 60 Minutes]

7. Set switch #6 to the OFF position.

The Display Module

Compact

Alarm Board

Dip-Switch

When you have completed step #7, the display module will

automatically go into “RESET” mode. This will store the data

that you entered.