Baumer BMxx, GBxxx-GXxxx - EtherCAT / PoE from version&nbsp,5.0 User Manual

Page 13

Advertising
background image

Baumer_EtherCAT_PoE_5-00_MA_EN.docx

13/30

www.baumer.com

30.09.14

Device-specific objects

Object Data in this area are hold volatile in RAM after any change. To save in non-volatile EEprom use
object SAVE Application Parameter 0x1010.

Object 0x6000 Operating parameters

SubIndex

0

Data Type

Unsigned 16

Access

ReadWrite

Default

0, scaling OFF, CW, Speed Value readout in steps /s

EEPROM

Yes

Significance

Operating parameters

Values

Bit 0: Direction of rotation

0 CW
1 CCW

Any parameter other than default will only become effective with enabled scaling function (0x6000).

Bit 2: Scaling function ON/OFF

0 scaling disabled, encoder provides raw data (w/o offset)
1 scaling enabled, encoder provides scaled, offset-related position values

Example: Value 0x0004 -> scaling On, CW

Bit 12: Unit for Speed Value readout

0 steps/s
1 rpm


User-settable parameters such as resolution, total measuring range, direction of rotation and preset
will not become effective until the scaling function is enabled (bit 2 =1).
See chapter parameterization.

The above parameters will be preliminarily saved in the volatile RAM memory and can optionally be saved
non-volatile in EEProm using object SAVE Application Parameter (0x1010).
Please note that with scaling ON the input data (TxPDO) will be produced much more slowly, i.e. PLC cycle
times for encoder readout should be correspondingly enlarged.
See chapter cycle times.

Object 0x6001 Measuring units per revolution

SubIndex

0

Data type

Unsigned 32

Access

ReadWrite

Default

0x2000 = 8192 = 13bit

GXxMW_H

0x1000 = 4096 = 12bit

GCxMW_H

0x40000 = 262144 = 18bit

GBxMW_H, GDxMW_H

EEPROM

Yes

Significance

Optional number of steps per revolution.

Values

1..n.. max. number of steps per revolution (0x6501)
Entries ≠ default values are only effective with enabled scaling function (0x6000).

In general, when writing on this object any previously saved offset (0x6509) will be cleared (value = 0).